Industry · Commercial · Controlled laboratory test

UL Controlled Lab Test — Trane 7.5-Ton RTU

Underwriters Laboratories measured a seven-year-old 7.5-ton Trane packaged rooftop unit under AHRI 340/360-2007 and ASHRAE 37-2009, treated it, ran it 400+ hours, then re-measured it under identical conditions.

All case studies
UL Controlled Lab Test — Trane 7.5-Ton RTU — Commercial HVAC site

Client Objective

Verify the current capacity and efficiency of a seven-year-old packaged rooftop unit against original equipment manufacturer design specifications.

Determine what material changes, if any, occur in that same unit after being treated with EnviroTemp.

Outcome & Benefits

The baseline established that the unit had lost a considerable amount of capacity and efficiency relative to its 90,000 BTU/h OEM design specification — measuring only 64,796 BTU/h.

After treatment and 400+ hours of full-load runtime, the same unit measured 77,060 BTU/h with EER improving from 6.50 to 7.96 while total measured power fell from 9.97 kW to 9.68 kW.

Physical condensate capture independently corroborated the capacity result, rising 24.6% in the same 30-minute collection window.

Verified evidence record

What was tested, and how

Equipment
2008 Trane 7.5-ton packaged rooftop unit, model TSC090A3EGAZUB
Age
7 years old at time of test (2008 unit, tested 2015)
Refrigerant
R-22, 9.80 lb charge (recovered, acid-tested and reinstalled to nameplate)
Initial condition
Considerable degraded capacity and efficiency loss versus OEM design specification: 64,796 BTU/h measured against 90,000 BTU/h design, EER 6.50 against 10.3 design.
Treatment
8 oz of EnviroTemp — matched to nominal design tonnage — injected into the evaporator section while the unit ran under load.
Runtime before final measurement
400+ hours at full load in a holding chamber before the post-treatment measurement.
Testing conditions
AHRI 340/360-2007 100% “A” test in an AHRI-certified dual psychrometric chamber: 95 °F DB / 75 °F WB outdoor, 80 °F DB / 67 °F WB entering evaporator air, 400 CFM per ton at design static pressure. Three 10-minute collection segments averaged, utility-grade power meters, NIST-certified hot-wire anemometer airflow verification per ASHRAE 37-2009 §7.7.
Source / documentation
UL LLC Laboratory Data Package — Project 4786820856, Sample 2030380-NW, Plano TX (TL-339)
View source documentation
Results Snapshot
Equipment Details
Make
Trane
Model
TSC090A3EGAZUB
Nominal size
7.5 ton packaged RTU
Refrigerant
R-22 (9.80 lb charge)
Electrical
208–230 V / 3 Ph / 60 Hz
Measured Points
Before
After
Δ
Total capacity
64,796 BTU/h
77,060 BTU/h
+18.9%
EER
6.50
7.96
+22.5%
Power draw
9.97 kW
9.68 kW
−2.9%
kW per ton
1.846
1.510
18.2% better
Cooling capacity
5.40 tons
6.42 tons
+18.9%
Condensate / 30 min
5.45 lbs
6.79 lbs
+24.6%
Outdoor air (held)
95.0 °F DB / 75.0 °F WB
95.0 °F DB / 75.0 °F WB

Controlled laboratory testing demonstrated measurable improvements in the tested system.

Results vary based on equipment condition, design, age, maintenance and operating conditions.

These are the measured results of one specific unit under one standardised protocol — not a guaranteed outcome for other equipment.