Independent case study

Simon Property Group Great Mall, Milpitas CA.

Detailed baseline and post measurements were taken on seven (7) nominal 35-ton Carrier rooftop units serving disperse areas of the property — verifying the financial savings, increased efficiency, and carbon footprint reductions delivered by ACFlush.

Energy reduction
21.3%
Avg kW after regression
More cooling
22.2%
Tons of cooling delivered
Payback
7.8 mo
Across 7 commercial RTUs
5-year ROI
667%
Project savings vs cost
Aerial view of the Great Mall rooftop showing commercial HVAC units

Demo particulars

Location
Milpitas, CA
Dates
13 May – 17 June
Equipment
7 × Carrier WeatherMaker 50A3-035LPH
Capacity
35-ton nominal each

Methodology

Protocol
IPMVP
Power monitoring
Continuous on 4 RTUs
Energy rate
$0.27 / kWh
Annual runtime
2,555 hours (conservative)

Project economics

Project cost
$19,600 ($2,800 × 7)
Annual savings
$30,054
Simple IRR
153%
Payback
7.83 months

Full results — RTU summary

All values calculated after regression analysis.

MetricBaselinePost-ACFlushChange
Avg kW (after regression)29.2022.98−21.3%
Total kWh522,308410,998−111,310
Total cost to operate$141,023$110,969−$30,054
Total capacity (tons)106.55130.25+22.2%
Avg kW / ton1.561.23−21.1%
Avg coefficient of performance2.292.89+26.2%
Avg EER7.819.87+26.3%
Avg SEER8.4311.18+32.6%

"Following treatment with the ECM, the 7 RTUs showed an average reduction of 21.3% in energy use while at the same time producing 22.2% more tons of cooling."

Tri-S Technologies · Independent verification report